-
1 well locations
2) Сахалин Р: размещение скважин -
2 well locations
Англо-русский словарь нефтегазовой промышленности > well locations
-
3 first conductor (short string of large casing used offshore and in marshy locations to keep top of well-bore open and provide means of conveying up-flowing drilling mud from well-bore to mud pit)
Нефтегазовая техника шахтовое направление скважиныУниверсальный англо-русский словарь > first conductor (short string of large casing used offshore and in marshy locations to keep top of well-bore open and provide means of conveying up-flowing drilling mud from well-bore to mud pit)
-
4 first conductor (short string of large casing used offshore and in marshy locations to keep top of well-bore open and provide means of conveying up-flowing drilling mud from well-bore to mud pit)
Англо-русский словарь нефтегазовой промышленности > first conductor (short string of large casing used offshore and in marshy locations to keep top of well-bore open and provide means of conveying up-flowing drilling mud from well-bore to mud pit)
-
5 some
1) немногие; отдельные2) некоторый / некоторыеto some extent в какой-то степени; в некоторой степени3) одни... ( в сочетаниях типа одни..., другие...)in some locations..., in other ( locations) в одних местах..., в других...;in some instances... and in others в одних случаях..., а в других случаях;at some facilities..., but other refineries... на одних нефтеперерабатывающих заводах..., в то время как на других -...;For some well conditions..., while other well conditions... Применительно к одним скважинным условиям..., в то время как для других скважин-ных условий...;Some soils fall apart in numerous small aggregations of particles, others may form... Одни грунты распадаются на большое количество мелких сгустков частиц, другие могут образовывать...4) тот или иной5) определенный (в знач. тот или иной)6) ряд (в знач. некоторые)some important characteristics ряд существенных характеристик7) \some в общих чертахEnglish-Russian dictionary of scientific and technical difficulties vocabulary > some
-
6 in
in accordance with 1. в соответствии сin accordance with good practice в соответствии с принятой / установившейся практикой 2. руководствуясь чем-л.in addition to that вместе с темin advance 1. заранее; заблаговременноSupplier shall notify the Contractor sufficiently in advance of any fabricating operations Обо всех производственных операциях Поставщик заблаговременно извещает Подрядчика 2. авансом (т.е. "вперед", в отличие от in arrears- см.)in all ways 1. во всех отношениях 2. с любой точки зренияin analysis based on limit load при расчете по предельным нагрузкамin anticipation 1. исподволь 2. заблаговременноin arrears по факту (т.е. по истечении какого-то времени, «потом», в отличие от in advance - см)in attendance Those in attendance included Присутствовали:...in basic terms вообще говоря; в общем и целом; как правилоin block letters печатными буквамиin the blueprint stage в стадии проектирования (перен. в стадии планирования, "на бумаге"; в отличие от in the hardware stage - см.)in bulk quantities в товарных количествахin case a (the)seal is disturbed при нарушении пломбыin case of eye contact при попадании в глаза (опасного / вредного вещества /материала)in case of ingestion при попадании внутрь (опасного / вредного вещества /материала)in case of inhalation при вдыхании (опасного / вредного вещества / материала)in case of respiratory standstill при остановке дыханияin case of skin contact при попадании на кожу (опасного /вредного вещества /материала)in case of swallowing при проглатывании (опасного /вредного вещества /материала)in the clear: be sure all personnel are in the clear убедиться в том, что весь персонал находится в безопасности (т.е. вне опасности, на безопасном расстоянии и т.д.)in codex form в форме книгиin compliance with по (напр., нормам, ТУ и т.д.);in compliance with your request по Вашей просьбеin conclusion, В заключение...in a condensed form в сжатой формеin conflict with: In conflict with this is... ( в начале предлож.) В то же время...; Вместе с тем...in conformance to по (напр., нормам, ТУ и т.д.)in conjunction with 1. параллельно сIn conjunction with an increase in rate, the tube position corresponding to... is located farther upstream Параллельно с увеличением скорости [ осадкообразования] сечение на трубке, соответствующее..., смещается все выше по потоку 2. одновременно с 3. в сочетании сin connection with 1. в свете... 2. в контексте чего-л. 3. in connection with Fig. 13... Если обратиться к рис. 13...in consideration of 1. принимая во внимание 2. учитываяin a conspicuous location на видном местеin a conspicuous place на видном местеin a conspicuous position на видном местеin consultation with по согласованию с; по договоренности сin contemplation of в преддверии чего-л.;in contemplation of our upcoming meeting в преддверии нашей предстоящей встречиin the context of 1. в связи с; в свете; в плане 2. применительно к 3. если иметь в виду; с учетом 4. на примере 5. с точки зрения 6. в случае 7. в отношении 8. в области 9. в рамкахin continuation of в развитие чего-л.in contradiction with противоречащий чему-л.if this is not in contradiction with если это не противоречит...in contrast (npomueum.) 1. жеIn contrast, the algorithm presented here... Предлагаемый же здесь метод... 2. что же касается...These studies have concentrated in the upper water layers... In contrast, rather little detailed work seems to have been undertaken in the very deepest parts of the[ Caspian] Sea Эти исследования проводились в основном в верхних слоях воды... Что же касается самых глубоких участков [ Каспийского] моря, то там, похоже, практически не проводилось сколько-нибудь детальных исследовательских работin contrast to в отличие от; в то время как; что же касаетсяin control не выходящий за установленные предельные значения (напр., о размерах, механических свойствах, технологических параметрах и т.д.)in a controlled manner организованноthe practice of burning off waste gas in a controlled manner установившаяся / принятая практика организованного сжигания сбросного газа [ в факеле]in a criss-cross pattern по перекрестной схеме ( затяжка болтов - для обеспечения равномерной затяжки)in a customary manner обычным способом; по обычной схеме; тривиальноA shall be determined in a customary manner А определяется обычным путем / по обычной схеме / тривиальноin a design situation при проектированииin diction словами; на обычном языке; открытым текстом (т.е. не кодом)in a direction parallel to по ходу (напр., трубопровода)in document format отдельным изданиемin domestic experience в отечественной практикеin due time в установленные сроки; своевременноin effect по существуin either direction в любом направленииin either direction parallel to the piping run в любом направлении по ходу трубопроводаwell in excess заведомо больше; с избыткомin excess of 1. не укладывающийся в 2. сверх чего-л.weld material in excess of the specified weld size избыток материала сварного шва сверх установленного размераin an expedient manner оперативноin fact более того,...in force действующий (напр., законодательство, договор и т.д.)in the field на монтаже ( а не па заводе или на производстве)in the first place вообщеin foreseeable future в обозримом будущемin formative stage в стадии становленияin free format в произвольном видеin full detail исчерпывающе; исчерпывающим образом; исчерпывающе подробно; с исчерпывающей полнотойin full standing полноправныйin full view в пределах прямой видимости (зд. «прямо» означает не впереди, перед, а незаслоненный, незагороженный)in furtherance of в продолжение чего-л.;in furtherance of our talks в продолжение нашего разговораin furtherance to в развитие чего-л.;in furtherance to your letter dated01.15.2004 в развитие Вашего письма от 15.01.2004 г.in general: A does not in general correspond to В А не всегда соответствует Вin general terms вообще говоряin the generic sense собирательноin good order в полной исправности; в исправном рабочем состоянии;in good working order в исправном рабочем состоянииin good standing полноправныйin a gradual manner плавно;pre-heat shall be applied in a gradual and uniform manner подогрев производится плавно и равномерноin greater detail намного / гораздо полнееquantity in hand наличные запасы;work in hand намеченная к выполнению работа; запланированная работа; заданная работаin hidden form (матем.) в неявном виде; в неявной формеin the initial stages на первых порахin isolation автономноin the judgment of по мнениюin line with 1. в увязке сin line with overall project requirements в увязке с потребностями проекта в целом 2. (перен.) в русле чего-л. 3. вдоль чего-л. 4. соосно с чем-л. 5. параллельно чему-л.in the long run в перспективеin a... manner: in a gradual and uniform manner плавно и равномерноin a masterful way мастерскиThe problem has been dealt with in a masterful way Поставленная задача решена мастерскиin the mean в обычном смыслеin the melting-pot: be in the melting-pot находиться в стадии решения / принятия решенияin a modification в другом исполненииin multiples of в количествеin the near term в краткосрочной перспективеin need of нуждающийся в чем-л.;those found to be in need of assistance те, кто определенно нуждаются в помощиin no case ни при каких обстоятельствахin a non-discriminative manner непредвзятоin no time в сжатые срокиin no way никоим образом неThe signing of this document by a Company agent shall in no way relieve the Manufacturer of any responsibility for Визирование / Факт подписания настоящего документа представителем Компании никоим образом не освобождает Поставщика от ответственности за;Inspection by the Contractor in no way relieves the Supplier of his responsibility to meet the requirements of... Проведение / Факт проведения контроля Подрядчиком никоим образом не освобождает Поставщика от ответственности за выполнение требований...in operation задействованный;which may fluctuate due to the number of fire water hydrants in operation который может колебаться в зависимости от числа задействованных пожарных гидрантовin an orderly manner организованно; в организованном порядкеin outline в общих чертахin one's own element в своей сфереin one's own milieu в своей сфереin particular в первую очередь; прежде всегоin passing заметим в скобках; заметим попутно; между прочимin person личноin place:1) be in place 1. иметь наготове; представлять (документы, согласования и т.д.) 2. (описат.) используемый (реально, фактически)2) have in place располагать (чем-л.)3) put in place 1. внедрять; вводить в действие; внедрять в практику 2. реализовывать 3. выполнять ( фактически); осуществлять 4. задействовать; (перен..) запускать (напр., процесс перехода на новый материал)in point:1) case in point характерный пример; образчик; эпизод2) tool in point подходящее / нужное / соответствующее средствоin the present circumstances 1. в данном случае 2. в этих условияхin print;Books in print (КВП) "Книги, имеющиеся в продаже" (а не в печати!)Since work is still in progress to define А Поскольку работа по определению А еще не завершена,...in pursuance of: 1. следуя (напр., нашему плану) 2. in pursuance of your letter dated01.15.2004 в связи с Вашим письмом от 15.01.2004 г.; в контексте Вашего письма от 15.01.2004 г. 3. in pursuance of your orders во исполнение Ваших указанийin pursuance to в ответ на;in pursuance to your letter в ответ на Ваше письмоin question рассматриваемыйin receipt of: We are in receipt of your letter dated Мы получили Ваше письмо от...in recent years в последние годыin recognition of 1. отдавая должное 2. принимая во внимание 3. с учетомin reference: in reference to your inquiry dated На Ваш запрос от...in this regard (синон. in this context) в этой связиin response of в соответствии с;in response of A comments against В в соответствии с замечаниями А по Вin response to в соответствии с;in response to crew comments against B1 unit в соответствии с замечаниями экипажа по блоку В1;in retaliation в отместку за что-л.in retrospect задним числомin routine use in: be in routine use in обычно используется вin running order годный к пуску (напр., блок электростанции)in a sense в известном смыслеin a short time в недалеком будущемin situ на своем местеin so far as коль скороin some instances... and in others в одних случаях..., а в других случаяхin some locations..., in other (locations) в одних местах..., в других...in spurts скачкообразный (напр., о росте трещины)in step with по мере (увеличения, уменьшения, роста, снижения, и т.д.];in step with the growth in GDP по мере роста / увеличения валового внутреннего продуктаin substitution to взамен чего-л. (напр., выдавать доработанный чертеж: проекта вместо другого, предыдущего)in summary в общем (и целом)in terms of (ЛДП) 1. в плане чего-л.; в части чего-л. 2. если говорить о 3. (матем.) относительноA can be written in terms of stress, displacement... А можно записать относительно напряжений, перемещений... 4. с точки зренияThe processes that... have been evaluated in terms of the reduction of total reactive nitrogen Процессы, которые..., оценивали с точки зрения снижения концентрации общего реакцион-носпособного азота 5. по...These zones were examined separately in terms of how they influenced the exhaust level of NOx Параметры каждой из этих зон исследовали раздельно по их влиянию на интенсивность образованияNOx 6. в вопросах... 7. в пересчете на 8. в соответствииin this context 1. здесь; в этом / данном случае; в этом смысле 2. в данной ситуации; в такой ситуации 3. в этой связи; в связи с этим 4. при этом условии 5. при такой постановке 6. в рамках; в светеin this instance А если это так, то; А раз это так, тоin a timely manner оперативноBureau of Land Management will make every effort to process applications for rights-of-way in a timely manner Управление земплепользования США примет все меры к оперативному рассмотрению заявлений на получение полосы отчуждения / отводаin a tough spot: be in a tough spot находиться / оказаться в затруднительном положенииin a uniform manner равномерноin unique cases в исключительных случаяхin unison параллельно; совместно; в связкеif a load is lifted by two or more trucks working in unison если перевалка груза осуществляется двумя или более самосвалами, работающими в связкеin use 1. принятый (в знач. находящийся в употреблении)standard operating procedure in use within the US обычная методика / обычный порядок работы, принятая / принятый в США 2. находящийся в обороте 3. at the locations where the equipment is in use в тех местах, где эта техника эксплуатируется / используется / задействуетсяin the vicinity of в зоне чего-л.;in the vicinity of fire в зоне огня ( пожара)in view of 1. в связи с; коль скоро; в свете чего-л.; на основании чего-л. in view of the foregoing в связи с вышеизложенным; в свете вышеизложенного; на основании вышеизложенного 2. in view of the fact that в связи с тем, чтоin which case и тогда...in witness whereof в удостоверение чего...in a workmanlike manner квалифицированно; мастерски; "классно"in writing в письменном видеin a wrong place 1. в неположенном месте 2. (разг.) не тамEnglish-Russian dictionary of scientific and technical difficulties vocabulary > in
-
7 first conductor
Нефтегазовая техника (short string of large casing used offshore and in marshy locations to keep top of well-bore open and provide means of conveying up-flowing drilling mud from well-bore to mud pit) шахтовое направление скважины -
8 courant admissible, m
(длительный) допустимый ток
Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их температуры в установившемся режиме
[ ГОСТ Р МЭК 60050-826-2009]
Этот ток обозначают IZ
[ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]EN
(continuous) current-carrying capacity
ampacity (US)
maximum value of electric current which can be carried continuously by a conductor, a device or an apparatus, under specified conditions without its steady-state temperature exceeding a specified value
[IEV number 826-11-13]
ampacity
The current in amperes that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
[National Electrical Cod]FR
courant (permanent) admissible, m
valeur maximale du courant électrique qui peut parcourir en permanence, un conducteur, un dispositif ou un appareil, sans que sa température de régime permanent, dans des conditions données, soit supérieure à la valeur spécifiée
[IEV number 826-11-13]Ampacity, the term is defined as the maximum amount of current a cable can carry before sustaining immediate or progressive deterioration. Also described as current rating or current-carrying capacity, is the RMS electric current which a device can continuously carry while remaining within its temperature rating. The ampacity of a cable depends on:
- its insulation temperature rating;
- conductor electrical properties for current;
- frequency, in the case of alternating currents;
- ability to dissipate heat, which depends on cable geometry and its surroundings;
- ambient temperature.
Electric wires have some resistance, and electric current flowing through them causes voltage drop and power dissipation, which heats the cable. Copper or aluminum can conduct a large amount of current before melting, but long before the conductors melt, their insulation would be damaged by the heat.
The ampacity for a power cable is thus based on physical and electrical properties of the material & construction of the conductor and of its insulation, ambient temperature, and environmental conditions adjacent to the cable. Having a large overall surface area may dissipate heat well if the environment can absorb the heat.
In a long run of cable, different conditions govern, and installation regulations normally specify that the most severe condition along the run governs the cable's rating. Cables run in wet or oily locations may carry a lower temperature rating than in a dry installation. Derating is necessary for multiple circuits in close proximity. When multiple cables are near, each contributes heat to the others and diminishes the amount of cooling air that can flow past the individual cables. The overall ampacity of the insulated conductors in a bundle of more than 3 must be derated, whether in a raceway or cable. Usually the de-rating factor is tabulated in a nation's wiring regulations.
Depending on the type of insulating material, common maximum allowable temperatures at the surface of the conductor are 60, 75 and 90 degrees Celsius, often with an ambient air temperature of 30°C. In the U.S., 105°C is allowed with ambient of 40°C, for larger power cables, especially those operating at more than 2 kV. Likewise, specific insulations are rated 150, 200 or 250°C.
The allowed current in cables generally needs to be decreased (derated) when the cable is covered with fireproofing material.
For example, the United States National Electric Code, Table 310-16, specifies that up to three 8 AWG copper wires having a common insulating material (THWN) in a raceway, cable, or direct burial has an ampacity of 50 A when the ambient air is 30°C, the conductor surface temperature allowed to be 75°C. A single insulated conductor in air has 70 A rating.
Ampacity rating is normally for continuous current, and short periods of overcurrent occur without harm in most cabling systems. The acceptable magnitude and duration of overcurrent is a more complex topic than ampacity.
When designing an electrical system, one will normally need to know the current rating for the following:- Wires
- Printed Circuit Board traces, where included
- Fuses
- Circuit breakers
- All or nearly all components used
Some devices are limited by power rating, and when this power rating occurs below their current limit, it is not necessary to know the current limit to design a system. A common example of this is lightbulb holders.
[http://en.wikipedia.org/wiki/Ampacity]
Тематики
- электротехника, основные понятия
Синонимы
EN
DE
- Dauerstrombelastbarkeit, f
- Strombelastbarkeit, f
FR
- courant admissible, m
- courant permanent admissible, m
Франко-русский словарь нормативно-технической терминологии > courant admissible, m
-
9 courant permanent admissible, m
(длительный) допустимый ток
Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их температуры в установившемся режиме
[ ГОСТ Р МЭК 60050-826-2009]
Этот ток обозначают IZ
[ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]EN
(continuous) current-carrying capacity
ampacity (US)
maximum value of electric current which can be carried continuously by a conductor, a device or an apparatus, under specified conditions without its steady-state temperature exceeding a specified value
[IEV number 826-11-13]
ampacity
The current in amperes that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
[National Electrical Cod]FR
courant (permanent) admissible, m
valeur maximale du courant électrique qui peut parcourir en permanence, un conducteur, un dispositif ou un appareil, sans que sa température de régime permanent, dans des conditions données, soit supérieure à la valeur spécifiée
[IEV number 826-11-13]Ampacity, the term is defined as the maximum amount of current a cable can carry before sustaining immediate or progressive deterioration. Also described as current rating or current-carrying capacity, is the RMS electric current which a device can continuously carry while remaining within its temperature rating. The ampacity of a cable depends on:
- its insulation temperature rating;
- conductor electrical properties for current;
- frequency, in the case of alternating currents;
- ability to dissipate heat, which depends on cable geometry and its surroundings;
- ambient temperature.
Electric wires have some resistance, and electric current flowing through them causes voltage drop and power dissipation, which heats the cable. Copper or aluminum can conduct a large amount of current before melting, but long before the conductors melt, their insulation would be damaged by the heat.
The ampacity for a power cable is thus based on physical and electrical properties of the material & construction of the conductor and of its insulation, ambient temperature, and environmental conditions adjacent to the cable. Having a large overall surface area may dissipate heat well if the environment can absorb the heat.
In a long run of cable, different conditions govern, and installation regulations normally specify that the most severe condition along the run governs the cable's rating. Cables run in wet or oily locations may carry a lower temperature rating than in a dry installation. Derating is necessary for multiple circuits in close proximity. When multiple cables are near, each contributes heat to the others and diminishes the amount of cooling air that can flow past the individual cables. The overall ampacity of the insulated conductors in a bundle of more than 3 must be derated, whether in a raceway or cable. Usually the de-rating factor is tabulated in a nation's wiring regulations.
Depending on the type of insulating material, common maximum allowable temperatures at the surface of the conductor are 60, 75 and 90 degrees Celsius, often with an ambient air temperature of 30°C. In the U.S., 105°C is allowed with ambient of 40°C, for larger power cables, especially those operating at more than 2 kV. Likewise, specific insulations are rated 150, 200 or 250°C.
The allowed current in cables generally needs to be decreased (derated) when the cable is covered with fireproofing material.
For example, the United States National Electric Code, Table 310-16, specifies that up to three 8 AWG copper wires having a common insulating material (THWN) in a raceway, cable, or direct burial has an ampacity of 50 A when the ambient air is 30°C, the conductor surface temperature allowed to be 75°C. A single insulated conductor in air has 70 A rating.
Ampacity rating is normally for continuous current, and short periods of overcurrent occur without harm in most cabling systems. The acceptable magnitude and duration of overcurrent is a more complex topic than ampacity.
When designing an electrical system, one will normally need to know the current rating for the following:- Wires
- Printed Circuit Board traces, where included
- Fuses
- Circuit breakers
- All or nearly all components used
Some devices are limited by power rating, and when this power rating occurs below their current limit, it is not necessary to know the current limit to design a system. A common example of this is lightbulb holders.
[http://en.wikipedia.org/wiki/Ampacity]
Тематики
- электротехника, основные понятия
Синонимы
EN
DE
- Dauerstrombelastbarkeit, f
- Strombelastbarkeit, f
FR
- courant admissible, m
- courant permanent admissible, m
Франко-русский словарь нормативно-технической терминологии > courant permanent admissible, m
-
10 réseau de communication
сеть связи
—
[http://www.rfcmd.ru/glossword/1.8/index.php?a=index&d=23]EN
communication network
system of communication nodes and links that provides transmission of analog or digital signals
EXAMPLES Telecommunications networks, Internet, intranet, extranet, Wide Area Networks (WAN), Local Area Networks (LAN) and computer networking utilizing information technology.
NOTE 1 A network has its boundary. All nodes at the network boundary are called ends. In some applications, the term “node” is used instead of “end” as a communication access point to the network, as well as for interconnections between the transmission links.
NOTE 2 A “backbone” communication network consists of core network and high-speed transmission lines (national or international), connecting between major switching network nodes (interconnection of transmission lines) at various locations in a country or region.
[IEC 61907, ed. 1.0 (2009-12)]FR
réseau de communication
système constitué de nœuds et de liaisons de communication assurant la transmission des signaux analogiques ou numériques
EXEMPLES Les réseaux de télécommunications, l’Internet, l'intranet, l’extranet, les réseaux étendus (WAN), les réseaux locaux (d'entreprise) (RLE) et les réseaux informatiques utilisant les technologies de l’information.
NOTE 1 Un réseau comporte sa propre frontière. L’ensemble des nœuds situés au niveau de la frontière d’un réseau s’appellent des terminaux. Dans certaines applications, le terme «nœud» est utilisé à la place du terme «terminal» comme point d'accès de communication au réseau, ainsi que pour désigner les interconnexions entre les liaisons de transmission.
NOTE 2 Un réseau de communication «fédérateur» est constitué d’un réseau central et de lignes de transmission à grande vitesse (nationales ou internationales) reliant entre eux des nœuds de réseaux de commutation importants (interconnexion de lignes de transmission) en divers lieux d'un pays ou d'une région.
[IEC 61907, ed. 1.0 (2009-12)]Тематики
EN
FR
Франко-русский словарь нормативно-технической терминологии > réseau de communication
-
11 Dauerstrombelastbarkeit, f
(длительный) допустимый ток
Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их температуры в установившемся режиме
[ ГОСТ Р МЭК 60050-826-2009]
Этот ток обозначают IZ
[ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]EN
(continuous) current-carrying capacity
ampacity (US)
maximum value of electric current which can be carried continuously by a conductor, a device or an apparatus, under specified conditions without its steady-state temperature exceeding a specified value
[IEV number 826-11-13]
ampacity
The current in amperes that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
[National Electrical Cod]FR
courant (permanent) admissible, m
valeur maximale du courant électrique qui peut parcourir en permanence, un conducteur, un dispositif ou un appareil, sans que sa température de régime permanent, dans des conditions données, soit supérieure à la valeur spécifiée
[IEV number 826-11-13]Ampacity, the term is defined as the maximum amount of current a cable can carry before sustaining immediate or progressive deterioration. Also described as current rating or current-carrying capacity, is the RMS electric current which a device can continuously carry while remaining within its temperature rating. The ampacity of a cable depends on:
- its insulation temperature rating;
- conductor electrical properties for current;
- frequency, in the case of alternating currents;
- ability to dissipate heat, which depends on cable geometry and its surroundings;
- ambient temperature.
Electric wires have some resistance, and electric current flowing through them causes voltage drop and power dissipation, which heats the cable. Copper or aluminum can conduct a large amount of current before melting, but long before the conductors melt, their insulation would be damaged by the heat.
The ampacity for a power cable is thus based on physical and electrical properties of the material & construction of the conductor and of its insulation, ambient temperature, and environmental conditions adjacent to the cable. Having a large overall surface area may dissipate heat well if the environment can absorb the heat.
In a long run of cable, different conditions govern, and installation regulations normally specify that the most severe condition along the run governs the cable's rating. Cables run in wet or oily locations may carry a lower temperature rating than in a dry installation. Derating is necessary for multiple circuits in close proximity. When multiple cables are near, each contributes heat to the others and diminishes the amount of cooling air that can flow past the individual cables. The overall ampacity of the insulated conductors in a bundle of more than 3 must be derated, whether in a raceway or cable. Usually the de-rating factor is tabulated in a nation's wiring regulations.
Depending on the type of insulating material, common maximum allowable temperatures at the surface of the conductor are 60, 75 and 90 degrees Celsius, often with an ambient air temperature of 30°C. In the U.S., 105°C is allowed with ambient of 40°C, for larger power cables, especially those operating at more than 2 kV. Likewise, specific insulations are rated 150, 200 or 250°C.
The allowed current in cables generally needs to be decreased (derated) when the cable is covered with fireproofing material.
For example, the United States National Electric Code, Table 310-16, specifies that up to three 8 AWG copper wires having a common insulating material (THWN) in a raceway, cable, or direct burial has an ampacity of 50 A when the ambient air is 30°C, the conductor surface temperature allowed to be 75°C. A single insulated conductor in air has 70 A rating.
Ampacity rating is normally for continuous current, and short periods of overcurrent occur without harm in most cabling systems. The acceptable magnitude and duration of overcurrent is a more complex topic than ampacity.
When designing an electrical system, one will normally need to know the current rating for the following:- Wires
- Printed Circuit Board traces, where included
- Fuses
- Circuit breakers
- All or nearly all components used
Some devices are limited by power rating, and when this power rating occurs below their current limit, it is not necessary to know the current limit to design a system. A common example of this is lightbulb holders.
[http://en.wikipedia.org/wiki/Ampacity]
Тематики
- электротехника, основные понятия
Синонимы
EN
DE
- Dauerstrombelastbarkeit, f
- Strombelastbarkeit, f
FR
- courant admissible, m
- courant permanent admissible, m
Немецко-русский словарь нормативно-технической терминологии > Dauerstrombelastbarkeit, f
-
12 Strombelastbarkeit, f
(длительный) допустимый ток
Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их температуры в установившемся режиме
[ ГОСТ Р МЭК 60050-826-2009]
Этот ток обозначают IZ
[ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]EN
(continuous) current-carrying capacity
ampacity (US)
maximum value of electric current which can be carried continuously by a conductor, a device or an apparatus, under specified conditions without its steady-state temperature exceeding a specified value
[IEV number 826-11-13]
ampacity
The current in amperes that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
[National Electrical Cod]FR
courant (permanent) admissible, m
valeur maximale du courant électrique qui peut parcourir en permanence, un conducteur, un dispositif ou un appareil, sans que sa température de régime permanent, dans des conditions données, soit supérieure à la valeur spécifiée
[IEV number 826-11-13]Ampacity, the term is defined as the maximum amount of current a cable can carry before sustaining immediate or progressive deterioration. Also described as current rating or current-carrying capacity, is the RMS electric current which a device can continuously carry while remaining within its temperature rating. The ampacity of a cable depends on:
- its insulation temperature rating;
- conductor electrical properties for current;
- frequency, in the case of alternating currents;
- ability to dissipate heat, which depends on cable geometry and its surroundings;
- ambient temperature.
Electric wires have some resistance, and electric current flowing through them causes voltage drop and power dissipation, which heats the cable. Copper or aluminum can conduct a large amount of current before melting, but long before the conductors melt, their insulation would be damaged by the heat.
The ampacity for a power cable is thus based on physical and electrical properties of the material & construction of the conductor and of its insulation, ambient temperature, and environmental conditions adjacent to the cable. Having a large overall surface area may dissipate heat well if the environment can absorb the heat.
In a long run of cable, different conditions govern, and installation regulations normally specify that the most severe condition along the run governs the cable's rating. Cables run in wet or oily locations may carry a lower temperature rating than in a dry installation. Derating is necessary for multiple circuits in close proximity. When multiple cables are near, each contributes heat to the others and diminishes the amount of cooling air that can flow past the individual cables. The overall ampacity of the insulated conductors in a bundle of more than 3 must be derated, whether in a raceway or cable. Usually the de-rating factor is tabulated in a nation's wiring regulations.
Depending on the type of insulating material, common maximum allowable temperatures at the surface of the conductor are 60, 75 and 90 degrees Celsius, often with an ambient air temperature of 30°C. In the U.S., 105°C is allowed with ambient of 40°C, for larger power cables, especially those operating at more than 2 kV. Likewise, specific insulations are rated 150, 200 or 250°C.
The allowed current in cables generally needs to be decreased (derated) when the cable is covered with fireproofing material.
For example, the United States National Electric Code, Table 310-16, specifies that up to three 8 AWG copper wires having a common insulating material (THWN) in a raceway, cable, or direct burial has an ampacity of 50 A when the ambient air is 30°C, the conductor surface temperature allowed to be 75°C. A single insulated conductor in air has 70 A rating.
Ampacity rating is normally for continuous current, and short periods of overcurrent occur without harm in most cabling systems. The acceptable magnitude and duration of overcurrent is a more complex topic than ampacity.
When designing an electrical system, one will normally need to know the current rating for the following:- Wires
- Printed Circuit Board traces, where included
- Fuses
- Circuit breakers
- All or nearly all components used
Some devices are limited by power rating, and when this power rating occurs below their current limit, it is not necessary to know the current limit to design a system. A common example of this is lightbulb holders.
[http://en.wikipedia.org/wiki/Ampacity]
Тематики
- электротехника, основные понятия
Синонимы
EN
DE
- Dauerstrombelastbarkeit, f
- Strombelastbarkeit, f
FR
- courant admissible, m
- courant permanent admissible, m
Немецко-русский словарь нормативно-технической терминологии > Strombelastbarkeit, f
-
13 FPA
- размещение рекламы в зоне проведения соревнований
- противопожарные действия
- вероятностный анализ отказа оборудования на АЭС
- акселератор арифметических операций с плавающей точкой
акселератор арифметических операций с плавающей точкой
—
[ http://www.iks-media.ru/glossary/index.html?glossid=2400324]Тематики
- электросвязь, основные понятия
EN
вероятностный анализ отказа оборудования на АЭС
—
[А.С.Гольдберг. Англо-русский энергетический словарь. 2006 г.]Тематики
EN
противопожарные действия
—
[А.С.Гольдберг. Англо-русский энергетический словарь. 2006 г.]Тематики
EN
размещение рекламы в зоне проведения соревнований
Размещение рекламы в зоне проведения соревнований во время Игр не допускается. Сложность осуществления Программы по размещению рекламы состоит в том, чтобы, с одной стороны, предоставить спонсорам хорошие места и возможности для рекламы своего бренда, а с другой – обеспечить чистоту и надлежащий вид игровых полей. Это достигается благодаря вовлечению спонсоров в Программу «Образ Игр». Игры являются единственным в мире крупным спортивным соревнованием, в рамках которого запрещается размещение рекламы на стадионах или одежде спортсменов.
[Департамент лингвистических услуг Оргкомитета «Сочи 2014». Глоссарий терминов]EN
field of play advertising (FPA)
No field of play advertising is permitted at the Games. The challenge of the FPA program is to ensure that sponsors are provided with the good branding opportunities and locations possible, while ensuring a clean and well-presented Field of Play that can be identified as being part of the Games. This is achieved through integrating sponsors into the Look of the Games program. The Games are the only major sporting event in the world, where there no advertising is allowed either in stadium or on athletes.
[Департамент лингвистических услуг Оргкомитета «Сочи 2014». Глоссарий терминов]Тематики
EN
Англо-русский словарь нормативно-технической терминологии > FPA
-
14 continuous current-carrying capacity
длительная пропускная способность по току
—
[Я.Н.Лугинский, М.С.Фези-Жилинская, Ю.С.Кабиров. Англо-русский словарь по электротехнике и электроэнергетике, Москва, 1999 г.]Тематики
- электротехника, основные понятия
EN
(длительный) допустимый ток
Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их температуры в установившемся режиме
[ ГОСТ Р МЭК 60050-826-2009]
Этот ток обозначают IZ
[ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]EN
(continuous) current-carrying capacity
ampacity (US)
maximum value of electric current which can be carried continuously by a conductor, a device or an apparatus, under specified conditions without its steady-state temperature exceeding a specified value
[IEV number 826-11-13]
ampacity
The current in amperes that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
[National Electrical Cod]FR
courant (permanent) admissible, m
valeur maximale du courant électrique qui peut parcourir en permanence, un conducteur, un dispositif ou un appareil, sans que sa température de régime permanent, dans des conditions données, soit supérieure à la valeur spécifiée
[IEV number 826-11-13]Ampacity, the term is defined as the maximum amount of current a cable can carry before sustaining immediate or progressive deterioration. Also described as current rating or current-carrying capacity, is the RMS electric current which a device can continuously carry while remaining within its temperature rating. The ampacity of a cable depends on:
- its insulation temperature rating;
- conductor electrical properties for current;
- frequency, in the case of alternating currents;
- ability to dissipate heat, which depends on cable geometry and its surroundings;
- ambient temperature.
Electric wires have some resistance, and electric current flowing through them causes voltage drop and power dissipation, which heats the cable. Copper or aluminum can conduct a large amount of current before melting, but long before the conductors melt, their insulation would be damaged by the heat.
The ampacity for a power cable is thus based on physical and electrical properties of the material & construction of the conductor and of its insulation, ambient temperature, and environmental conditions adjacent to the cable. Having a large overall surface area may dissipate heat well if the environment can absorb the heat.
In a long run of cable, different conditions govern, and installation regulations normally specify that the most severe condition along the run governs the cable's rating. Cables run in wet or oily locations may carry a lower temperature rating than in a dry installation. Derating is necessary for multiple circuits in close proximity. When multiple cables are near, each contributes heat to the others and diminishes the amount of cooling air that can flow past the individual cables. The overall ampacity of the insulated conductors in a bundle of more than 3 must be derated, whether in a raceway or cable. Usually the de-rating factor is tabulated in a nation's wiring regulations.
Depending on the type of insulating material, common maximum allowable temperatures at the surface of the conductor are 60, 75 and 90 degrees Celsius, often with an ambient air temperature of 30°C. In the U.S., 105°C is allowed with ambient of 40°C, for larger power cables, especially those operating at more than 2 kV. Likewise, specific insulations are rated 150, 200 or 250°C.
The allowed current in cables generally needs to be decreased (derated) when the cable is covered with fireproofing material.
For example, the United States National Electric Code, Table 310-16, specifies that up to three 8 AWG copper wires having a common insulating material (THWN) in a raceway, cable, or direct burial has an ampacity of 50 A when the ambient air is 30°C, the conductor surface temperature allowed to be 75°C. A single insulated conductor in air has 70 A rating.
Ampacity rating is normally for continuous current, and short periods of overcurrent occur without harm in most cabling systems. The acceptable magnitude and duration of overcurrent is a more complex topic than ampacity.
When designing an electrical system, one will normally need to know the current rating for the following:- Wires
- Printed Circuit Board traces, where included
- Fuses
- Circuit breakers
- All or nearly all components used
Some devices are limited by power rating, and when this power rating occurs below their current limit, it is not necessary to know the current limit to design a system. A common example of this is lightbulb holders.
[http://en.wikipedia.org/wiki/Ampacity]
Тематики
- электротехника, основные понятия
Синонимы
EN
DE
- Dauerstrombelastbarkeit, f
- Strombelastbarkeit, f
FR
- courant admissible, m
- courant permanent admissible, m
Англо-русский словарь нормативно-технической терминологии > continuous current-carrying capacity
-
15 ampacity (US)
(длительный) допустимый ток
Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их температуры в установившемся режиме
[ ГОСТ Р МЭК 60050-826-2009]
Этот ток обозначают IZ
[ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]EN
(continuous) current-carrying capacity
ampacity (US)
maximum value of electric current which can be carried continuously by a conductor, a device or an apparatus, under specified conditions without its steady-state temperature exceeding a specified value
[IEV number 826-11-13]
ampacity
The current in amperes that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
[National Electrical Cod]FR
courant (permanent) admissible, m
valeur maximale du courant électrique qui peut parcourir en permanence, un conducteur, un dispositif ou un appareil, sans que sa température de régime permanent, dans des conditions données, soit supérieure à la valeur spécifiée
[IEV number 826-11-13]Ampacity, the term is defined as the maximum amount of current a cable can carry before sustaining immediate or progressive deterioration. Also described as current rating or current-carrying capacity, is the RMS electric current which a device can continuously carry while remaining within its temperature rating. The ampacity of a cable depends on:
- its insulation temperature rating;
- conductor electrical properties for current;
- frequency, in the case of alternating currents;
- ability to dissipate heat, which depends on cable geometry and its surroundings;
- ambient temperature.
Electric wires have some resistance, and electric current flowing through them causes voltage drop and power dissipation, which heats the cable. Copper or aluminum can conduct a large amount of current before melting, but long before the conductors melt, their insulation would be damaged by the heat.
The ampacity for a power cable is thus based on physical and electrical properties of the material & construction of the conductor and of its insulation, ambient temperature, and environmental conditions adjacent to the cable. Having a large overall surface area may dissipate heat well if the environment can absorb the heat.
In a long run of cable, different conditions govern, and installation regulations normally specify that the most severe condition along the run governs the cable's rating. Cables run in wet or oily locations may carry a lower temperature rating than in a dry installation. Derating is necessary for multiple circuits in close proximity. When multiple cables are near, each contributes heat to the others and diminishes the amount of cooling air that can flow past the individual cables. The overall ampacity of the insulated conductors in a bundle of more than 3 must be derated, whether in a raceway or cable. Usually the de-rating factor is tabulated in a nation's wiring regulations.
Depending on the type of insulating material, common maximum allowable temperatures at the surface of the conductor are 60, 75 and 90 degrees Celsius, often with an ambient air temperature of 30°C. In the U.S., 105°C is allowed with ambient of 40°C, for larger power cables, especially those operating at more than 2 kV. Likewise, specific insulations are rated 150, 200 or 250°C.
The allowed current in cables generally needs to be decreased (derated) when the cable is covered with fireproofing material.
For example, the United States National Electric Code, Table 310-16, specifies that up to three 8 AWG copper wires having a common insulating material (THWN) in a raceway, cable, or direct burial has an ampacity of 50 A when the ambient air is 30°C, the conductor surface temperature allowed to be 75°C. A single insulated conductor in air has 70 A rating.
Ampacity rating is normally for continuous current, and short periods of overcurrent occur without harm in most cabling systems. The acceptable magnitude and duration of overcurrent is a more complex topic than ampacity.
When designing an electrical system, one will normally need to know the current rating for the following:- Wires
- Printed Circuit Board traces, where included
- Fuses
- Circuit breakers
- All or nearly all components used
Some devices are limited by power rating, and when this power rating occurs below their current limit, it is not necessary to know the current limit to design a system. A common example of this is lightbulb holders.
[http://en.wikipedia.org/wiki/Ampacity]
Тематики
- электротехника, основные понятия
Синонимы
EN
DE
- Dauerstrombelastbarkeit, f
- Strombelastbarkeit, f
FR
- courant admissible, m
- courant permanent admissible, m
Англо-русский словарь нормативно-технической терминологии > ampacity (US)
-
16 continuous current
(длительный) допустимый ток
Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их температуры в установившемся режиме
[ ГОСТ Р МЭК 60050-826-2009]
Этот ток обозначают IZ
[ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]EN
(continuous) current-carrying capacity
ampacity (US)
maximum value of electric current which can be carried continuously by a conductor, a device or an apparatus, under specified conditions without its steady-state temperature exceeding a specified value
[IEV number 826-11-13]
ampacity
The current in amperes that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
[National Electrical Cod]FR
courant (permanent) admissible, m
valeur maximale du courant électrique qui peut parcourir en permanence, un conducteur, un dispositif ou un appareil, sans que sa température de régime permanent, dans des conditions données, soit supérieure à la valeur spécifiée
[IEV number 826-11-13]Ampacity, the term is defined as the maximum amount of current a cable can carry before sustaining immediate or progressive deterioration. Also described as current rating or current-carrying capacity, is the RMS electric current which a device can continuously carry while remaining within its temperature rating. The ampacity of a cable depends on:
- its insulation temperature rating;
- conductor electrical properties for current;
- frequency, in the case of alternating currents;
- ability to dissipate heat, which depends on cable geometry and its surroundings;
- ambient temperature.
Electric wires have some resistance, and electric current flowing through them causes voltage drop and power dissipation, which heats the cable. Copper or aluminum can conduct a large amount of current before melting, but long before the conductors melt, their insulation would be damaged by the heat.
The ampacity for a power cable is thus based on physical and electrical properties of the material & construction of the conductor and of its insulation, ambient temperature, and environmental conditions adjacent to the cable. Having a large overall surface area may dissipate heat well if the environment can absorb the heat.
In a long run of cable, different conditions govern, and installation regulations normally specify that the most severe condition along the run governs the cable's rating. Cables run in wet or oily locations may carry a lower temperature rating than in a dry installation. Derating is necessary for multiple circuits in close proximity. When multiple cables are near, each contributes heat to the others and diminishes the amount of cooling air that can flow past the individual cables. The overall ampacity of the insulated conductors in a bundle of more than 3 must be derated, whether in a raceway or cable. Usually the de-rating factor is tabulated in a nation's wiring regulations.
Depending on the type of insulating material, common maximum allowable temperatures at the surface of the conductor are 60, 75 and 90 degrees Celsius, often with an ambient air temperature of 30°C. In the U.S., 105°C is allowed with ambient of 40°C, for larger power cables, especially those operating at more than 2 kV. Likewise, specific insulations are rated 150, 200 or 250°C.
The allowed current in cables generally needs to be decreased (derated) when the cable is covered with fireproofing material.
For example, the United States National Electric Code, Table 310-16, specifies that up to three 8 AWG copper wires having a common insulating material (THWN) in a raceway, cable, or direct burial has an ampacity of 50 A when the ambient air is 30°C, the conductor surface temperature allowed to be 75°C. A single insulated conductor in air has 70 A rating.
Ampacity rating is normally for continuous current, and short periods of overcurrent occur without harm in most cabling systems. The acceptable magnitude and duration of overcurrent is a more complex topic than ampacity.
When designing an electrical system, one will normally need to know the current rating for the following:- Wires
- Printed Circuit Board traces, where included
- Fuses
- Circuit breakers
- All or nearly all components used
Some devices are limited by power rating, and when this power rating occurs below their current limit, it is not necessary to know the current limit to design a system. A common example of this is lightbulb holders.
[http://en.wikipedia.org/wiki/Ampacity]
Тематики
- электротехника, основные понятия
Синонимы
EN
DE
- Dauerstrombelastbarkeit, f
- Strombelastbarkeit, f
FR
- courant admissible, m
- courant permanent admissible, m
непрерывный ток
—
[Я.Н.Лугинский, М.С.Фези-Жилинская, Ю.С.Кабиров. Англо-русский словарь по электротехнике и электроэнергетике, Москва, 1999]Тематики
- электротехника, основные понятия
EN
Англо-русский словарь нормативно-технической терминологии > continuous current
-
17 current-carrying capacity
(длительный) допустимый ток
Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их температуры в установившемся режиме
[ ГОСТ Р МЭК 60050-826-2009]
Этот ток обозначают IZ
[ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]EN
(continuous) current-carrying capacity
ampacity (US)
maximum value of electric current which can be carried continuously by a conductor, a device or an apparatus, under specified conditions without its steady-state temperature exceeding a specified value
[IEV number 826-11-13]
ampacity
The current in amperes that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
[National Electrical Cod]FR
courant (permanent) admissible, m
valeur maximale du courant électrique qui peut parcourir en permanence, un conducteur, un dispositif ou un appareil, sans que sa température de régime permanent, dans des conditions données, soit supérieure à la valeur spécifiée
[IEV number 826-11-13]Ampacity, the term is defined as the maximum amount of current a cable can carry before sustaining immediate or progressive deterioration. Also described as current rating or current-carrying capacity, is the RMS electric current which a device can continuously carry while remaining within its temperature rating. The ampacity of a cable depends on:
- its insulation temperature rating;
- conductor electrical properties for current;
- frequency, in the case of alternating currents;
- ability to dissipate heat, which depends on cable geometry and its surroundings;
- ambient temperature.
Electric wires have some resistance, and electric current flowing through them causes voltage drop and power dissipation, which heats the cable. Copper or aluminum can conduct a large amount of current before melting, but long before the conductors melt, their insulation would be damaged by the heat.
The ampacity for a power cable is thus based on physical and electrical properties of the material & construction of the conductor and of its insulation, ambient temperature, and environmental conditions adjacent to the cable. Having a large overall surface area may dissipate heat well if the environment can absorb the heat.
In a long run of cable, different conditions govern, and installation regulations normally specify that the most severe condition along the run governs the cable's rating. Cables run in wet or oily locations may carry a lower temperature rating than in a dry installation. Derating is necessary for multiple circuits in close proximity. When multiple cables are near, each contributes heat to the others and diminishes the amount of cooling air that can flow past the individual cables. The overall ampacity of the insulated conductors in a bundle of more than 3 must be derated, whether in a raceway or cable. Usually the de-rating factor is tabulated in a nation's wiring regulations.
Depending on the type of insulating material, common maximum allowable temperatures at the surface of the conductor are 60, 75 and 90 degrees Celsius, often with an ambient air temperature of 30°C. In the U.S., 105°C is allowed with ambient of 40°C, for larger power cables, especially those operating at more than 2 kV. Likewise, specific insulations are rated 150, 200 or 250°C.
The allowed current in cables generally needs to be decreased (derated) when the cable is covered with fireproofing material.
For example, the United States National Electric Code, Table 310-16, specifies that up to three 8 AWG copper wires having a common insulating material (THWN) in a raceway, cable, or direct burial has an ampacity of 50 A when the ambient air is 30°C, the conductor surface temperature allowed to be 75°C. A single insulated conductor in air has 70 A rating.
Ampacity rating is normally for continuous current, and short periods of overcurrent occur without harm in most cabling systems. The acceptable magnitude and duration of overcurrent is a more complex topic than ampacity.
When designing an electrical system, one will normally need to know the current rating for the following:- Wires
- Printed Circuit Board traces, where included
- Fuses
- Circuit breakers
- All or nearly all components used
Some devices are limited by power rating, and when this power rating occurs below their current limit, it is not necessary to know the current limit to design a system. A common example of this is lightbulb holders.
[http://en.wikipedia.org/wiki/Ampacity]
Тематики
- электротехника, основные понятия
Синонимы
EN
DE
- Dauerstrombelastbarkeit, f
- Strombelastbarkeit, f
FR
- courant admissible, m
- courant permanent admissible, m
предельно допустимый ток
—
[Я.Н.Лугинский, М.С.Фези-Жилинская, Ю.С.Кабиров. Англо-русский словарь по электротехнике и электроэнергетике, Москва, 1999 г.]Тематики
- электротехника, основные понятия
EN
прочность печатной платы к токовой нагрузке
Свойство печатной платы сохранять электрические и механические характеристики после воздействия максимально допустимой токовой нагрузки на печатный проводник или металлизированное отверстие печатной платы.
[ ГОСТ Р 53386-2009]Тематики
EN
Англо-русский словарь нормативно-технической терминологии > current-carrying capacity
-
18 remain over night (RON)
остановка с ночевкой
Данный термин охватывает все мероприятия и виды деятельности, осуществляемые в пункте, где Эстафета Олимпийского огня и обслуживающий ее персонал остаются на ночлег в гостиницах, расположенных по маршруту движения эстафеты. В каждой такой гостинице команде эстафеты предоставляются размещение и трехразовое питание, а также организуется временный командный пункт для подготовки следующего этапа эстафеты.
[Департамент лингвистических услуг Оргкомитета «Сочи 2014». Глоссарий терминов]EN
remain over night (RON)
It refers to all operations and activities that occur at the site where the flame and OTR staff stay for the night. This term refers to overnight hotel locations along the OTR route. Each RON location will provide accommodations and primary meals, as well as act as the temporary, static command post and staging area for the OTR.
[Департамент лингвистических услуг Оргкомитета «Сочи 2014». Глоссарий терминов]Тематики
EN
Англо-русский словарь нормативно-технической терминологии > remain over night (RON)
-
19 field of play advertising
размещение рекламы в зоне проведения соревнований
Размещение рекламы в зоне проведения соревнований во время Игр не допускается. Сложность осуществления Программы по размещению рекламы состоит в том, чтобы, с одной стороны, предоставить спонсорам хорошие места и возможности для рекламы своего бренда, а с другой – обеспечить чистоту и надлежащий вид игровых полей. Это достигается благодаря вовлечению спонсоров в Программу «Образ Игр». Игры являются единственным в мире крупным спортивным соревнованием, в рамках которого запрещается размещение рекламы на стадионах или одежде спортсменов.
[Департамент лингвистических услуг Оргкомитета «Сочи 2014». Глоссарий терминов]EN
field of play advertising (FPA)
No field of play advertising is permitted at the Games. The challenge of the FPA program is to ensure that sponsors are provided with the good branding opportunities and locations possible, while ensuring a clean and well-presented Field of Play that can be identified as being part of the Games. This is achieved through integrating sponsors into the Look of the Games program. The Games are the only major sporting event in the world, where there no advertising is allowed either in stadium or on athletes.
[Департамент лингвистических услуг Оргкомитета «Сочи 2014». Глоссарий терминов]Тематики
EN
Англо-русский словарь нормативно-технической терминологии > field of play advertising
-
20 communication network
сеть связи
—
[http://www.rfcmd.ru/glossword/1.8/index.php?a=index&d=23]EN
communication network
system of communication nodes and links that provides transmission of analog or digital signals
EXAMPLES Telecommunications networks, Internet, intranet, extranet, Wide Area Networks (WAN), Local Area Networks (LAN) and computer networking utilizing information technology.
NOTE 1 A network has its boundary. All nodes at the network boundary are called ends. In some applications, the term “node” is used instead of “end” as a communication access point to the network, as well as for interconnections between the transmission links.
NOTE 2 A “backbone” communication network consists of core network and high-speed transmission lines (national or international), connecting between major switching network nodes (interconnection of transmission lines) at various locations in a country or region.
[IEC 61907, ed. 1.0 (2009-12)]FR
réseau de communication
système constitué de nœuds et de liaisons de communication assurant la transmission des signaux analogiques ou numériques
EXEMPLES Les réseaux de télécommunications, l’Internet, l'intranet, l’extranet, les réseaux étendus (WAN), les réseaux locaux (d'entreprise) (RLE) et les réseaux informatiques utilisant les technologies de l’information.
NOTE 1 Un réseau comporte sa propre frontière. L’ensemble des nœuds situés au niveau de la frontière d’un réseau s’appellent des terminaux. Dans certaines applications, le terme «nœud» est utilisé à la place du terme «terminal» comme point d'accès de communication au réseau, ainsi que pour désigner les interconnexions entre les liaisons de transmission.
NOTE 2 Un réseau de communication «fédérateur» est constitué d’un réseau central et de lignes de transmission à grande vitesse (nationales ou internationales) reliant entre eux des nœuds de réseaux de commutation importants (interconnexion de lignes de transmission) en divers lieux d'un pays ou d'une région.
[IEC 61907, ed. 1.0 (2009-12)]Тематики
EN
FR
Англо-русский словарь нормативно-технической терминологии > communication network
- 1
- 2
См. также в других словарях:
Well logging — Gamma ray logging Spontaneous potential logging Resistivity logging Density logging Sonic logging Caliper logging Mud logging LWD/MWD v · … Wikipedia
Locations of Half-Life — The Half Life series of video games features many locations set in a dystopian future stemming from the events of the first game, Half Life. These locations are used and referred to throughout the series. The locations, for the most part, are… … Wikipedia
Locations in the Half-Life series — The Half Life series of video games features many locations set in an dystopian future stemming from the events of the first game, Half Life . These locations are used and referred to throughout the series. The locations, for the most part, are… … Wikipedia
Locations in Veronica Mars — Veronica Mars is an American television series created by Rob Thomas.[1] The series premiered on September 22, 2004, during UPN s last two years, and ended on May 22, 2007, after a season on UPN s successor, The CW Television Network.[2] Set in… … Wikipedia
Well smack — Sectional drawing of well smack[1] A well smack is a type of traditional fishing boat that has a well amidships. The well was filled with circulated external water, which kept fish alive until delivered to land and sold. It was a modified form of … Wikipedia
Well car — A double stack car owned by the TTX Company. The 53 ft (16.15 m) capacity car is a Gunderson Maxi IV. The containers are owned by Pacer Stacktrain. A well car, also known as a double stack car or stack car, is a type of railroad car… … Wikipedia
List of locations of the DC Universe — Locations in the DC Universe, the shared universe setting of DC Comics.ites* Arkham Asylum for the Criminally Insane. Located in Gotham City. * Arrowcave, former base of operations of Green Arrow and Speedy. * Batcave, headquarters of Batman.… … Wikipedia
List of reportedly haunted locations — This is a list of locations reportedly haunted by ghosts or other supernatural beings. Reports of haunted locations are part of ghostlore. Ghostlore is fueled by history and legend and is part of folklore.Australia * The Alkimos is a shipwreck of … Wikipedia
List of After Colony locations — This is a list of fictional locations from the After Colony timeline of the Gundam anime metaseries. Please note that this list includes resource satellites and other phenomenae resulting from space colonization, but not space fortresses or space … Wikipedia
List of locations in The Simpsons — This list of locations in The Simpsons includes towns, cities, businesses, states, and other locations created for the television series The Simpsons. This list only includes places that exist solely in the Simpsons universe, not real life… … Wikipedia
List of A Series of Unfortunate Events locations — This is a list of fictional locations that appear in the children s book series A Series of Unfortunate Events, by Lemony Snicket. Contents 1 Geographic locations 1.1 Hinterlands 1.2 Mortmain Mountains … Wikipedia